J-H(St)H FE180 PH120 Fire Resistant Cable
Product Code: J-H(St)H FE180 PH120
| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form |
| 3 – Stranding | : | In layers up to 10 pairs, 20 pairs to 100 pairs consist of stranding of 10 pair groups wrapped with polypropylene identification tape |
| 4 – Wrapping | : | A non-hygroscopic and dielectric polyester tape is applied on the cable core longitudinally or helically. (More than 10 pairs) |
| 5 – Fire Barrier | : | Glass yarn tape |
| 6 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 7 – Outer Jacket | : | UV resistant halogen-free outer jacket. |
| Conductor Diameter |
Conductor Resistance Ω/km (20 °C) |
Insulation Resistance (@500V DC) MΩ/km |
Operating Voltage V DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|
| 0.40 mm | 146.6 | 100 | 250 | 1000 |
| 0.50 mm | 93.0 | 100 | 250 | 1000 |
| 0.60 mm | 64.6 | 100 | 250 | 1000 |
| 0.80 mm | 37.0 | 100 | 250 | 1000 |
| 0.90 mm | 28.8 | 100 | 250 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) |
Circuit Integrity with Shock Test (PH120) |
|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |