RE-2X(St)H FE180 Fire Resistant Cable

Product Code: RE-2X(St)H FE180

  • Cable Construction
  • Technical Data
  • Standards
  • Mechanical Characteristics
1 – Conductor : Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 – Wrapping : Each conductor wrapped with mica tape
3 – Insulation : XLPE (BS EN 50290-2, VDE 0207 YI1)
4 – Stranding : In layers
5 – Wrapping : Polyester tape
6 – Screen : Tinned copper earthing wire, Al/PET tape
7 – Outer Jacket : UV resistant halogen-free outer jacket.
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km

Operating
Voltage

V DC

Test Voltage

(@ 1 minute)
V DC

0.50 mm² 36.0 Min. 1000 Max. 250 300 2000
0.75 mm² 24.5 Min. 1000 Max. 250 300 2000
1.00 mm² 18.1 Min. 1000 Max. 250 300 2000
1.50 mm² 12.1 Min. 1000 Max. 250 300 2000
2.50 mm² 7.41 Min. 1000 Max. 250 300 2000
Smoke Density Test Corrosive Gas Test Halogen-free Test Flame Propagation Test Flame Retardancy Test Fire Resistance Test
(FE180)
IEC 61034-2,
VDE 0482-1034-2,
BS EN 61034-2
IEC 60754-2,
VDE 0482-267-2-3,
BS EN 50267-2-3
IEC 60754-1,
VDE 0482-267-2-1,
BS EN 50267-2-1
IEC 60332-3-24,
VDE 0482-332-3-24,
EN 60332-2-24
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
IEC 60331-21
Bending Radius Temperature Range
Operating
10xD mm -30°C ~ +90°C