RE-2X(St)H FE180 Fire Resistant Cable
Product Code: RE-2X(St)H FE180
| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Wrapping | : | Each conductor wrapped with mica tape |
| 3 – Insulation | : | XLPE (BS EN 50290-2, VDE 0207 YI1) |
| 4 – Stranding | : | In layers |
| 5 – Wrapping | : | Polyester tape |
| 6 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 7 – Outer Jacket | : | UV resistant halogen-free outer jacket. |
| Conductor Diameter |
Conductor Resistance Ω/km (20 °C) |
Insulation Resistance (@500V DC) MΩ/km |
Mutual Capacitance
nF/km |
Operating Voltage V DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|---|
| 0.50 mm² | 36.0 | Min. 1000 | Max. 250 | 300 | 2000 |
| 0.75 mm² | 24.5 | Min. 1000 | Max. 250 | 300 | 2000 |
| 1.00 mm² | 18.1 | Min. 1000 | Max. 250 | 300 | 2000 |
| 1.50 mm² | 12.1 | Min. 1000 | Max. 250 | 300 | 2000 |
| 2.50 mm² | 7.41 | Min. 1000 | Max. 250 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test | Fire Resistance Test (FE180) |
|---|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
IEC 60331-21 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -30°C ~ +90°C |