RE-2G(St)HSWBH-TP&TT FE180 Fire Resistant Cable
Product Code: RE-2G(St)HSWBH-TP&TT FE180
| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form |
| 3 – Stranding | : | Insulations are stranding into pairs or triads |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Inner Jacket | : | UV resistant halogen-free inner jacket. |
| 7 – Armor | : | Galvanized steel wire braiding |
| 8 – Outer Jacket | : | UV resistant halogen-free outer jacket. |
| Conductor Diameter |
Conductor Resistance Ω/km (20 °C) |
Insulation Resistance (@500V DC) MΩ/km |
Operating Voltage V DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|
| 0.50 mm² | 36.0 | 100 | 300 | 2000 |
| 0.75 mm² | 24.5 | 100 | 300 | 2000 |
| 1.00 mm² | 18.1 | 100 | 300 | 2000 |
| 1.50 mm² | 12.1 | 100 | 300 | 2000 |
| 2.50 mm² | 7.41 | 100 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test | Fire Resistance Test (FE180) |
|---|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
IEC 60331-21 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |