EIB-2Y(St)H BUS Cable
Product Code: EIB-2Y(St)H
| 1 – Conductor | : | Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228) |
| 2 – Insulation | : | Polyethylene compound (VDE 0815, EN 50290-2-26) |
| 3 – Stranding | : | Two pairs are stranded into a star-quad, above two pairs are stranded together in layers |
| 4 – Wrapping | : | Polyester tape |
| 5 – Screen | : | Tinned copper earthing wire, Al/PET tape |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 6018 (Green) |
| Conductor Diameter |
Conductor Resistance Ω/km (20 °C) |
Insulation Resistance (@500V DC) MΩ/km |
Mutual Capacitance
nF/km |
Operating Voltage V DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|---|
| 0.60 mm | 130.0 | 5000 | 100 | 300 | 800 |
| 0.80 mm | 73.2 | 5000 | 100 | 300 | 800 |
| 1.00 mm | 44.6 | 5000 | 100 | 300 | 1000 |
| 1.50 mm² | 24.6 | 5000 | 100 | 300 | 1000 |
| 2.50 mm² | 15.1 | 5000 | 100 | 300 | 1000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -30°C ~ +70°C |