Product Categories

RE-2Y(St)Y Instrumentation Cable

Product Code:

  • Cable Construction
  • Technical Data
  • Standards
  • Mechanical Characteristics
1 – Conductor : Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
2 – Insulation : Polyethylene (BS EN 50290-2, VDE 0207 YI1), White; Number coded (BS 5308-2)
3 – Stranding : In layers
4 – Wrapping : Polyester tape
5 – Screen : Tinned copper earthing wire, Al/PET tape
6 – Outer Jacket : UV resistant PVC outer jacket. RAL 9005 (Black)
Conductor
Diameter
Conductor Resistance
Ω/km
(20 °C)
Insulation
Resistance
(@500V DC)
MΩ/km
Mutual Capacitance

nF/km

Operating
Voltage

V DC

Test Voltage

(@ 1 minute)
V DC

0.50 mm² 36.0 5000 160 300/500 2000
0.75 mm² 24.5 5000 160 300/500 2000
1.00 mm² 18.1 5000 170 300/500 2000
1.50 mm² 12.1 5000 170 300/500 2000
2.50 mm² 7.41 5000 170 300/500 2000
Manufacturing Referance Flame Retardancy Test
EN 50288-7
or
IEC 60502-1
IEC 60332-1-2
Bending Radius Temperature Range
Operating
7.5xD mm -30°C ~ +70°C