Product Categories

LI2YCYSWBY-TP/TT Signal Control Cable

Product Code: LI2YCYSWBY-TP/TT

  • Cable Construction
  • Technical Data
  • Standards
  • Mechanical Characteristics
1 – Conductor : Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
2 – Insulation : Solid polyethylene (EN 50290-2-23, BS 6234 Type 03 – ASTM D 1248) (DIN 47100)
3 – Stranding : Insulations are stranded into pairs or triads and all pairs or triads are stranded together.
4 – Wrapping : Polyester tape
5 – Screen : Tinned copper braiding
6 – Inner Jacket : UV resistant PVC inner jacket. RAL 7035 (Grey)
7 – Armor : Galvanized steel wire braiding
8 – Outer Jacket : UV resistant PVC outer jacket. RAL 7035 (Grey)
Cross
Section
Conductor Resistance
(20 °C)
Ω/km
Insulation
Resistance
(20 °C)
MΩ/km
Mutual Capacitance

nF/km

Operating
Voltage

V DC

Test Voltage

(@ 1 minute)
V DC

0.22 mm² 85.0 5000 110 250 1200
0.25 mm² 77.8 5000 110 250 1200
0.34 mm² 56.0 5000 110 250 1200
0.50 mm² 39.0 5000 120 300/500 2000
0.75 mm² 26.0 5000 120 300/500 2000
1.00 mm² 19.5 5000 130 300/500 2000
1.50 mm² 13.3 5000 140 300/500 2000
2.50 mm² 7.98 5000 150 300/500 2000
Flame Retardancy Test
IEC 60332-1-2,
VDE 0482-332-1-2,
BS EN 60332-1-2
Bending Radius Temperature Range
Operating
7.5xD mm -30°C ~ +70°C