| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | Cross-linked polymer compound in ceramic form (DIN 47100) |
| 3 – Stranding | : | Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers. |
| 4 – Wrapping | : | Polyester tape, glass yarn tape |
| 5 – Screen | : | Al/PET, tinned copper braiding |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 2008 (Orange) |
| Conductor Diameter |
Conductor Resistance Ω/km (20 °C) |
Insulation Resistance (@500V DC) MΩ/km |
Mutual Capacitance
nF/km |
Operating VoltageV DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|---|
| 0.50 mm² | 39.0 | 100 | 100 | 300 | 2000 |
| 0.75 mm² | 26.0 | 100 | 100 | 300 | 2000 |
| 1.00 mm² | 19.5 | 100 | 100 | 300 | 2000 |
| 1.50 mm² | 13.3 | 100 | 100 | 300 | 2000 |
| 2.50 mm² | 8.0 | 100 | 100 | 300 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Circuit Integrity Test (FE180) |
Circuit Integrity with Shock Test (PH120) |
|---|---|
| IEC 60331-21 | EN 50200, VDE 0482-200, BS EN 50200 |
| Part Number | Pair Count | Conductor Diameter (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.536.2.4.3.0050.0.0001 | 1 | 0,5 | 5,7 | 17,1 | 48 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0002 | 2 | 0,5 | 7,3 | 28,9 | 74 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0003 | 3 | 0,5 | 8,3 | 39,7 | 95 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0004 | 4 | 0,5 | 10,1 | 52,2 | 129 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0005 | 5 | 0,5 | 10,6 | 61,6 | 146 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0006 | 6 | 0,5 | 11,2 | 71,4 | 167 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0007 | 7 | 0,5 | 12,2 | 81,6 | 191 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0008 | 8 | 0,5 | 12,6 | 91,8 | 209 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0009 | 9 | 0,5 | 13,3 | 101,2 | 231 | 100/500/1000 |
| 3.536.2.4.3.0050.0.0010 | 10 | 0,5 | 13,9 | 116,7 | 254 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.536.2.4.3.0075.0.0001 | 1 | 0,75 | 6,2 | 22,9 | 58 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0002 | 2 | 0,75 | 8,1 | 38,8 | 92 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0003 | 3 | 0,75 | 9,3 | 57,4 | 125 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0004 | 4 | 0,75 | 11,2 | 71,3 | 162 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0005 | 5 | 0,75 | 11,7 | 84,8 | 184 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0006 | 6 | 0,75 | 12,4 | 99,4 | 211 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0007 | 7 | 0,75 | 13,4 | 114,5 | 242 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0008 | 8 | 0,75 | 14 | 134,4 | 271 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0009 | 9 | 0,75 | 14,7 | 148,2 | 299 | 100/500/1000 |
| 3.536.2.4.3.0075.0.0010 | 10 | 0,75 | 15,4 | 164,1 | 324 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.536.2.4.3.0100.0.0001 | 1 | 1 | 6,5 | 25,6 | 63 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0002 | 2 | 1 | 8,5 | 46,3 | 103 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0003 | 3 | 1 | 9,8 | 66,4 | 139 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0004 | 4 | 1 | 11,9 | 85,8 | 183 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0005 | 5 | 1 | 12,4 | 102,7 | 209 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0006 | 6 | 1 | 13,1 | 120,9 | 241 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0007 | 7 | 1 | 14,3 | 144,6 | 282 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0008 | 8 | 1 | 14,8 | 161,6 | 309 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0009 | 9 | 1 | 15,6 | 181 | 344 | 100/500/1000 |
| 3.536.2.4.3.0100.0.0010 | 10 | 1 | 16,3 | 198,4 | 371 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.536.2.4.3.0150.0.0001 | 1 | 1,5 | 7,3 | 36,3 | 82 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0002 | 2 | 1,5 | 9,5 | 66,3 | 133 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0003 | 3 | 1,5 | 10,9 | 94,5 | 179 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0004 | 4 | 1,5 | 13,3 | 124,9 | 238 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0005 | 5 | 1,5 | 14 | 155,9 | 283 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0006 | 6 | 1,5 | 14,7 | 183,9 | 323 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0007 | 7 | 1,5 | 16 | 213 | 372 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0008 | 8 | 1,5 | 16,6 | 239,6 | 410 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0009 | 9 | 1,5 | 17,5 | 266,4 | 455 | 100/500/1000 |
| 3.536.2.4.3.0150.0.0010 | 10 | 1,5 | 18,3 | 296,1 | 496 | 100/500/1000 |
| Part Number | Pair Count | Conductor Diameter (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|
| 3.536.2.4.3.0250.0.0001 | 1 | 2,5 | 8,4 | 56,2 | 111 | 100/500/1000 |
| 3.536.2.4.3.0250.0.0002 | 2 | 2,5 | 11,2 | 104,5 | 188 | 100/500/1000 |
| 3.536.2.4.3.0250.0.0003 | 3 | 2,5 | 13 | 150,7 | 259 | 100/500/1000 |
| 3.536.2.4.3.0250.0.0004 | 4 | 2,5 | 15,9 | 204,6 | 349 | 100/500/1000 |
| 3.536.2.4.3.0250.0.0005 | 5 | 2,5 | 16,6 | 251 | 409 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 10xD mm | -40°C ~ +70°C |