LIH(St)CH-TP/TT Signal Control Cable
Product Code: LIH(St)CH-TP/TT
| 1 – Conductor | : | Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295) |
| 2 – Insulation | : | Halogen-free (TS IEC 60189-2, EN 50290-2-26) (DIN 47100) |
| 3 – Stranding | : | Insulations are stranded into pairs or triads and all pairs or triads are stranded together. |
| 4 – Wrapping | : | Polyester tape |
| 5 – Screen | : | Al/PET tape, tinned copper braiding |
| 6 – Outer Jacket | : | UV resistant halogen-free outer jacket. RAL 7035 (Grey) |
| Cross Section |
Conductor Resistance (20 °C) Ω/km |
Insulation Resistance (20 °C) MΩ/km |
Mutual Capacitance
nF/km |
Operating VoltageV DC |
Test Voltage
(@ 1 minute) |
|---|---|---|---|---|---|
| 0.22 mm² | 85.0 | 200 | 110 | 250 | 1200 |
| 0.25 mm² | 77.8 | 200 | 110 | 250 | 1200 |
| 0.34 mm² | 56.0 | 200 | 110 | 250 | 1200 |
| 0.50 mm² | 39.0 | 20 | 120 | 300/500 | 2000 |
| 0.75 mm² | 26.0 | 20 | 120 | 300/500 | 2000 |
| 1.00 mm² | 19.5 | 20 | 130 | 300/500 | 2000 |
| 1.50 mm² | 13.3 | 20 | 140 | 300/500 | 2000 |
| 2.50 mm² | 7.98 | 20 | 150 | 300/500 | 2000 |
| Smoke Density Test | Corrosive Gas Test | Halogen-free Test | Flame Propagation Test | Flame Retardancy Test |
|---|---|---|---|---|
| IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2 |
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3 |
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1 |
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24 |
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2 |
| Part Number | Conductor Count | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.538.2.3.3.0050.0.0001 | – | 1 | 0,5 | 5,2 | 14,3 | 35 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0002 | – | 2 | 0,5 | 6,7 | 24,8 | 56 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0003 | – | 3 | 0,5 | 7,7 | 35,1 | 73 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0004 | – | 4 | 0,5 | 9,5 | 46,4 | 102 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0005 | – | 5 | 0,5 | 9,9 | 55,5 | 117 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0006 | – | 6 | 0,5 | 10,5 | 64,7 | 134 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0007 | – | 7 | 0,5 | 11,4 | 75,1 | 155 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0008 | – | 8 | 0,5 | 11,9 | 84,1 | 171 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0009 | – | 9 | 0,5 | 12,6 | 94,4 | 191 | 100/500/1000 |
| 3.538.2.3.3.0050.0.0010 | – | 10 | 0,5 | 13,1 | 103,6 | 207 | 100/500/1000 |
| Part Number | Conductor Count | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.538.2.3.3.0075.0.0001 | – | 1 | 0,75 | 5,7 | 18,9 | 43 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0002 | – | 2 | 0,75 | 7,5 | 34,7 | 72 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0003 | – | 3 | 0,75 | 8,6 | 49,2 | 98 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0004 | – | 4 | 0,75 | 10,6 | 65,1 | 132 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0005 | – | 5 | 0,75 | 11 | 79,3 | 152 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0006 | – | 6 | 0,75 | 11,7 | 92,8 | 176 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0007 | – | 7 | 0,75 | 12,7 | 107,7 | 203 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0008 | – | 8 | 0,75 | 13,2 | 121,4 | 224 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0009 | – | 9 | 0,75 | 14 | 136,6 | 250 | 100/500/1000 |
| 3.538.2.3.3.0075.0.0010 | – | 10 | 0,75 | 14,6 | 150,4 | 272 | 100/500/1000 |
| Part Number | Conductor Count | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.538.2.3.3.0100.0.0001 | – | 1 | 1 | 6,1 | 23,3 | 50 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0002 | – | 2 | 1 | 8,1 | 42 | 84 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0003 | – | 3 | 1 | 9,3 | 60,1 | 115 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0004 | – | 4 | 1 | 11,4 | 79,5 | 154 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0005 | – | 5 | 1 | 11,9 | 97,4 | 179 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0006 | – | 6 | 1 | 12,7 | 114,4 | 207 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0007 | – | 7 | 1 | 13,8 | 131,7 | 239 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0008 | – | 8 | 1 | 14,4 | 150,3 | 266 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0009 | – | 9 | 1 | 15,2 | 167,5 | 296 | 100/500/1000 |
| 3.538.2.3.3.0100.0.0010 | – | 10 | 1 | 15,8 | 184,8 | 322 | 100/500/1000 |
| Part Number | Conductor Count | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.538.2.3.3.0150.0.0001 | – | 1 | 1,5 | 6,8 | 33 | 65 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0002 | – | 2 | 1,5 | 9 | 61,8 | 111 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0003 | – | 3 | 1,5 | 10,5 | 89,2 | 153 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0004 | – | 4 | 1,5 | 12,8 | 118,4 | 205 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0005 | – | 5 | 1,5 | 13,4 | 144,6 | 240 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0006 | – | 6 | 1,5 | 14,2 | 172,5 | 281 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0007 | – | 7 | 1,5 | 15,5 | 199,5 | 324 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0008 | – | 8 | 1,5 | 16,2 | 225,9 | 360 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0009 | – | 9 | 1,5 | 17,1 | 252,6 | 401 | 100/500/1000 |
| 3.538.2.3.3.0150.0.0010 | – | 10 | 1,5 | 17,8 | 281,4 | 440 | 100/500/1000 |
| Part Number | Conductor Count | Pair Count | Conductor Cross-section (mm²) | Approx. Cable Diameter (mm) | Copper Weight (kg/km) | Approx. Weight (kg/km) | Packing Lengths (m) |
|---|---|---|---|---|---|---|---|
| 3.538.2.3.3.0250.0.0001 | – | 1 | 2,5 | 8 | 51,9 | 92 | 100/500/1000 |
| 3.538.2.3.3.0250.0.0002 | – | 2 | 2,5 | 10,8 | 99,1 | 161 | 100/500/1000 |
| 3.538.2.3.3.0250.0.0003 | – | 3 | 2,5 | 12,6 | 144,2 | 226 | 100/500/1000 |
| 3.538.2.3.3.0250.0.0004 | – | 4 | 2,5 | 15,4 | 191 | 302 | 100/500/1000 |
| 3.538.2.3.3.0250.0.0005 | – | 5 | 2,5 | 16,2 | 234,8 | 357 | 100/500/1000 |
| Bending Radius | Temperature Range Operating |
|---|---|
| 7.5xD mm | -30°C ~ +70°C |