EIB-H(St)H BUS Cable cable, stripped back to show its construction

Building automation cable

EIB-H(St)H BUS Cable

Available as 5 part numbers from 0.60 mm to 2.50 mm². Full construction and technical data are in the datasheet.

Foil screened

Conductor size

Camcom part no.

739600FS

0.60 mm · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Six layers, from copper out.

Cross-section of EIB-H(St)H BUS Cable
  1. 1

    Conductor

    Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)

  2. 2

    Insulation

    Halogen-free compound (VDE 0815, EN 50290-2-26)

  3. 3

    Stranding

    Two pairs are stranded into a star-quad, above two pairs are stranded together in layers

  4. 4

    Wrapping

    Polyester tape

  5. 5

    Screen

    Tinned copper earthing wire, Al/PET tape

  6. 6

    Outer jacket

    UV resistant halogen-free outer jacket. RAL 6018 (Green)

Technical data

The numbers behind it.

Electrical · 0.60 mm

Conductor diameter
0.60 mm
Conductor resistance (20 °C)
130.0 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Mutual capacitance
100 nF/km
Operating voltage
300 V DC
Test voltage (@ 1 minute)
800 V DC

Mechanical

Bending radius
10xD mm
Temperature range operating
-30°C ~ +70°C

Standards

Smoke density test

IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2

Corrosive gas test

IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3

Halogen-free test

IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1

Flame propagation test

IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24

Flame retardancy test

IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
739600FS0.60 mmPDF ↓
739800FS0.80 mmPDF ↓
739100FS1.00 mmPDF ↓
731500FS1.50 mm²PDF ↓
732500FS2.50 mm²PDF ↓