Building management system cable
3C 14AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
14 AWG (19x27) Bare Copper
- 2
No. of conductors
3
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.011 in (0.28 mm)
- 5
Insulation diameter
0.092 in (2.3 mm)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.017 in (0.43 mm)
- 10
Cable diameter
0.245 in (6.22 mm)
Technical data
The numbers behind it.
Electrical · 2703FS
- Nom. conductor DCR
- 2.54 Ohm/1000ft (8.33 Ohm/km)
- Nom. capacitance Cond-to-Cond
- 83 pF/ft (270 pF/m)
- Nom. capacitance Cond-to-Other
- 149.4 pF/ft (490.2 pF/m)
- Nom. inductance
- 0.15 µH/ft (0.49 µH/m)
- Max. current
- 8 Amps per Conductor at 25ºC
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- 0°C To +75°C
- Min. bending radius
- 2.45 in (62.2 mm)
- Max. pull tension
- 151 lbs (68.5 kg)
- Approx. weight
- 51 lbs/1000ft (76 kg/km)
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.