Fibre optic cable
A-V(ZN)H(SR)T2Y
Indoor Fiber Optic Cable, available as 20 part numbers from 2F SM G.652.D to 12F OM3. Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
866002BAA
2F SM G.652.D · 1,000 m
Stock and lead time: ask us by email.
Construction
Ten layers, from the core out.

- 1
Optical fiber core
- 2
HFFR insulated tight-buffered fiber of
- 3
900 μm diameter
- 4
Non-metallic strength member (Glass yarn or aramid yarn)
- 5
UV resistant halogen-free (LSOH) black inner jacket.
- 6
Ripcord
- 7
Corrugated steel tape
- 8
Web
- 9
Steel messenger wire
- 10
UV resistant polyethylene black outer jacket
Technical data
The numbers behind it.
Mechanical
- Minimum bending radius – operation
- 20 x cable Ø
- Minimum bending radius – fixed
- 15 x cable Ø
- Temperature range – storage
- -40°C to + 70°C
- Temperature range – installation
- -30°C to +60°C
- Temperature range – transport
- -40°C to + 70°C
- Temperature range – operating
- -40°C to +70°C
Marking, Packing & Delivery
- Marking
- CAMCOM – Date of Manufacture – Fiber Count and Type – Length Marking
- Packing
- Wooden drum with protection
- Delivery lengths
- 2 km, 4 km ± 5 % tolerance
Mechanical & Environmental Characteristics
| Test Standard | Specified Value | Acceptance Criteria | |
|---|---|---|---|
| Maximum Installation Tension ² | IEC 60794-1-2-E1 | 1.0 x W(N), min. 1500 N | Fiber strain ≤ 0.33% |
| Maximum Operation Tension | IEC 60794-1-2-E1 | 0.5 x W(N), min. 750 N | Δα ≤ 0.05 dB, No fiber strain |
| Crush Strength | IEC 60794-1-2-E3 | 1000 N / 100 mm, maks. 10 min | Δα ≤ 0.05 dB, No damage |
| Impact | IEC 60794-1-2-E4 | 10 Nm, 3 impacts, R= 300 mm | Δα ≤ 0.05 dB after the test |
| Torsion | IEC 60794-1-2-E7 | 1 m, 100N, +/- 180°, 10 cycles | Δα ≤ 0.05 dB, No damage |
| Repeated Bending | IEC 60794-1-2-E6 | R=20x D, 100 N, 35 cycles | No damage |
| Bending Radius | IEC 60794-1-2-E11 | R=20x D, 4 turns, 3 cycles | Δα ≤ 0.05 dB, No damage |
| Temperature Cycling | IEC 60794-1-2-F1 | -20°C to +70°C | Δα ≤ 0.05 dB/km |
From the Camcom datasheet. The datasheet for the chosen part number is the reference.
Cable type data
Every size, one part number each.
| Camcom part no. | Conductor size | Datasheet |
|---|---|---|
| 866002BAA | 2F SM G.652.D | PDF ↓ |
| 866004BAA | 4F SM G.652.D | PDF ↓ |
| 866006BAA | 6F SM G.652.D | PDF ↓ |
| 866008BAA | 8F SM G.652.D | PDF ↓ |
| 866012BAA | 12F SM G.652.D | PDF ↓ |
| 861002BAA | 2F OM1 | PDF ↓ |
| 861004BAA | 4F OM1 | PDF ↓ |
| 861006BAA | 6F OM1 | PDF ↓ |
| 861008BAA | 8F OM1 | PDF ↓ |
| 861012BAA | 12F OM1 | PDF ↓ |
| 862002BAA | 2F OM2 | PDF ↓ |
| 862004BAA | 4F OM2 | PDF ↓ |
| 862006BAA | 6F OM2 | PDF ↓ |
| 862008BAA | 8F OM2 | PDF ↓ |
| 862012BAA | 12F OM2 | PDF ↓ |
| 863002BAA | 2F OM3 | PDF ↓ |
| 863004BAA | 4F OM3 | PDF ↓ |
| 863006BAA | 6F OM3 | PDF ↓ |
| 863008BAA | 8F OM3 | PDF ↓ |
| 863012BAA | 12F OM3 | PDF ↓ |