J-H(St)H FE180 PH120 cable, stripped back to show its construction

Fire resistant cable

J-H(St)H FE180 PH120

Available as 5 part numbers from 0.40 mm to 0.90 mm. Full construction and technical data are in the datasheet.

Foil screened

Conductor size

Camcom part no.

539400FS

0.40 mm · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Seven layers, from copper out.

Cross-section of J-H(St)H FE180 PH120
  1. 1

    Conductor

    Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)

  2. 2

    Insulation

    Cross-linked polymer compound in ceramic form

  3. 3

    Stranding

    In layers up to 10 pairs, 20 pairs to 100 pairs consist of stranding of 10 pair groups wrapped with polypropylene identification tape

  4. 4

    Wrapping

    A non-hygroscopic and dielectric polyester tape is applied on the cable core longitudinally or helically. (More than 10 pairs)

  5. 5

    Fire barrier

    Glass yarn tape

  6. 6

    Screen

    Tinned copper earthing wire, Al/PET tape

  7. 7

    Outer jacket

    UV resistant halogen-free outer jacket.

Technical data

The numbers behind it.

Electrical · 0.40 mm

Conductor diameter
0.40 mm
Conductor resistance (20 °C)
146.6 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Operating voltage
250 V DC
Test voltage (@ 1 minute)
1000 V DC

Mechanical

Bending radius
10xD mm
Temperature range operating
-40°C ~ +70°C

Standards

Circuit integrity test (FE180)

IEC 60331-21

Circuit integrity with shock test

EN 50200, VDE 0482-200,

(PH120) BS EN 50200

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
539400FS0.40 mmPDF ↓
539500FS0.50 mmPDF ↓
539600FS0.60 mmPDF ↓
539800FS0.80 mmPDF ↓
539900FS0.90 mmPDF ↓