Fire-resistant power cable
(N)HXH-J 0.6/1kV FE180 E90 Fire Resistant Cable
Available as 11 part numbers from 0.50 mm² to 35.00 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
530500UN
0.50 mm² · 1,000 m
Stock and lead time: ask us by email.
Construction
Six layers, from copper out.

- 1
Conductor
Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228).
- 2
Wrapping
Each conductor wrapped with mica tape.
- 3
Insulation
Wrapped conductors insulated with VDE 0266 HXI1 Cross-linked HFFR compound.
- 4
Stranding
Insulations are stranded into layers.
- 5
Filling
Halogen-free compund.
- 6
Outer jacket
UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Technical data
The numbers behind it.
Electrical · 0.50 mm²
- Cross section
- 0.50 mm²
- Conductor resistance (20 °C)
- 36.0 Ω/km
- Operating voltage
- 600/1000 V DC
- Test voltage (@ 1 minute)
- 4000 V
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 10xD mm
- Temperature range operating
- -40°C ~ +90°C
Standards
Circuit integrity test (FE180)
IEC 60331-21
Cable system circuit integrity test (E30
DIN 4102-12
E60 / E90)
From the Camcom datasheet. The datasheet for the chosen part number is the reference.
Cable type data