(N)HXH-J 0.6/1kV FE180 E90 Fire Resistant Cable cable, stripped back to show its construction

Fire-resistant power cable

(N)HXH-J 0.6/1kV FE180 E90 Fire Resistant Cable

Available as 11 part numbers from 0.50 mm² to 35.00 mm². Full construction and technical data are in the datasheet.

Unshielded

Conductor size

Camcom part no.

530500UN

0.50 mm² · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Six layers, from copper out.

Cross-section of (N)HXH-J 0.6/1kV FE180 E90 Fire Resistant Cable
  1. 1

    Conductor

    Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228).

  2. 2

    Wrapping

    Each conductor wrapped with mica tape.

  3. 3

    Insulation

    Wrapped conductors insulated with VDE 0266 HXI1 Cross-linked HFFR compound.

  4. 4

    Stranding

    Insulations are stranded into layers.

  5. 5

    Filling

    Halogen-free compund.

  6. 6

    Outer jacket

    UV resistant halogen-free outer jacket. RAL 2008 (Orange)

Technical data

The numbers behind it.

Electrical · 0.50 mm²

Cross section
0.50 mm²
Conductor resistance (20 °C)
36.0 Ω/km
Operating voltage
600/1000 V DC
Test voltage (@ 1 minute)
4000 V

Mechanical

Bending radius
10xD mm
Temperature range operating
-40°C ~ +90°C

Standards

Circuit integrity test (FE180)

IEC 60331-21

Cable system circuit integrity test (E30

DIN 4102-12

E60 / E90)

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
530500UN0.50 mm²PDF ↓
530700UN0.75 mm²PDF ↓
531000UN1.00 mm²PDF ↓
531500UN1.50 mm²PDF ↓
532500UN2.50 mm²PDF ↓
534000UN4.00 mm²PDF ↓
536000UN6.00 mm²PDF ↓
538100UN10.00 mm²PDF ↓
538200UN16.00 mm²PDF ↓
538300UN25.00 mm²PDF ↓
538400UN35.00 mm²PDF ↓