RE-H(St)HSWAH-PiMF/TiMF cable, stripped back to show its construction

Instrumentation cable

RE-H(St)HSWAH-PiMF/TiMF

Available as 5 part numbers from 0.50 mm² to 2.50 mm². Full construction and technical data are in the datasheet.

Individually screened

Conductor size

Camcom part no.

430550ISA

0.50 mm² · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Eleven layers, from copper out.

Cross-section of RE-H(St)HSWAH-PiMF/TiMF
  1. 1

    Conductor

    Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)

  2. 2

    Insulation

    Halogen-free (BS EN 50290-2, VDE 0207 YI1), Black, White, Red; Number coded (BS 5308-2)

  3. 3

    Individual stranding

    Insulations stranding into pairs or triads

  4. 4

    Individual wrapping

    Polyester tape

  5. 5

    Individual screen

    Tinned copper earthing wire, Al/PET tape

  6. 6

    Overall stranding

    Screened pairs or triads are stranded in layers.

  7. 7

    Overall wrapping

    Polyester tape

  8. 8

    Overall screen

    Tinned copper earthing wire, Al/PET tape

  9. 9

    Inner jacket

    Halogen-free inner jacket. RAL 9005 (Black)

  10. 10

    Armor

    Galvanized steel wire armor, polyester tape

  11. 11

    Outer jacket

    UV resistant halogen-free outer jacket. RAL 9005 (Black)

Technical data

The numbers behind it.

Electrical · 0.50 mm²

Conductor diameter
0.50 mm²
Conductor resistance (20 °C)
36.0 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Mutual capacitance
100 nF/km
Operating voltage
300/500 V DC
Test voltage (@ 1 minute)
2000 V DC

Mechanical

Bending radius
7.5xD mm
Temperature range operating
-30°C ~ +70°C

Standards

Manufacturing referance

EN 50288-7 or IEC 60502-1

Smoke density test

IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2

Corrosive gas test

IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3

Halogen-free test

IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1

Flame propagation test

IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24

Flame retardancy test

IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
430550ISA0.50 mm²PDF ↓
430750ISA0.75 mm²PDF ↓
431050ISA1.00 mm²PDF ↓
431550ISA1.50 mm²PDF ↓
432550ISA2.50 mm²PDF ↓