LI2Y(St)CH-TP/TT
LSZH Signal Control Cable, available as 8 part numbers from 0.22 mm² to 2.50 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
330250FBE
0.22 mm² · 1,000 m
Stock and lead time: ask us by email.
Construction
Six layers, from copper out.

- 1
Conductor
Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
- 2
Insulation
Solid polyethylene (EN 50290-2-23, BS 6234 Type 03 – ASTM D 1248) (DIN 47100)
- 3
Stranding
Insulations are stranded into pairs or triads and all pairs or triads are stranded together
- 4
Wrapping
Polyester tape
- 5
Screen
Al/PET tape, tinned copper braiding
- 6
Outer jacket
UV resistant halogen-free outer jacket. RAL 7035 (Grey)
Technical data
The numbers behind it.
Electrical · 0.22 mm²
- Cross section
- 0.22 mm²
- Conductor resistance (20 °C)
- 85.0 Ω/km
- Insulation resistance (20 °C)
- 5000 MΩ/km
- Mutual capacitance
- 110 nF/km
- Operating voltage
- 250 V DC
- Test voltage (@ 1 minute)
- 1200 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 7.5xD mm
- Temperature range operating
- -30°C ~ +70°C
Standards
Smoke density test
IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2
Corrosive gas test
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3
Halogen-free test
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1
Flame propagation test
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24
Flame retardancy test
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2
From the Camcom datasheet. The datasheet for the chosen part number is the reference.