Signal control cable
LI2Y(St)CHSWAH-PiMF/TiMF
LSZH Signal Control Cable, available as 8 part numbers from 0.22 mm² to 2.50 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
330250IBP
0.22 mm² · 1,000 m
Stock and lead time: ask us by email.
Construction
Ten layers, from copper out.

- 1
Conductor
Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
- 2
Insulation
Solid polyethylene (EN 50290-2-23, BS 6234 Type 03 – ASTM D 1248) (DIN 47100)
- 3
Stranding
Screened pairs or triads are stranded in layers.
- 4
Individual wrapping
Polyester tape
- 5
Individual screen
Tinned copper earthing wire, Al/PET tape
- 6
Wrapping
Polyester tape
- 7
Screen
Al/PET tape, tinned copper braiding
- 8
Inner jacket
UV resistant halogen-free inner jacket. RAL 7035 (Grey)
- 9
Armor
Galvanized steel wire armor, polyester tape
- 10
Outer jacket
UV resistant halogen-free outer jacket. RAL 7035 (Grey)
Technical data
The numbers behind it.
Electrical · 0.22 mm²
- Cross section
- 0.22 mm²
- Conductor resistance (20 °C)
- 85.0 Ω/km
- Insulation resistance (20 °C)
- 5000 MΩ/km
- Mutual capacitance
- 110 nF/km
- Operating voltage
- 250 V DC
- Test voltage (@ 1 minute)
- 1200 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 7.5xD mm
- Temperature range operating
- -30°C ~ +70°C
Standards
Smoke density test
IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2
Corrosive gas test
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3
Halogen-free test
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1
Flame propagation test
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24
Flame retardancy test
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2
From the Camcom datasheet. The datasheet for the chosen part number is the reference.