Building automation cable
EIB-Y(St)Y BUS Cable
Available as 5 part numbers from 0.60 mm to 2.50 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
729600FS
0.60 mm · 1,000 m
Stock and lead time: ask us by email.
Construction
Six layers, from copper out.

- 1
Conductor
Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)
- 2
Insulation
PVC compound (VDE 0815, EN 50290-2-21)
- 3
Stranding
Two pairs are stranded into a star-quad, above two pairs are stranded together in layers
- 4
Wrapping
Polyester tape
- 5
Screen
Tinned copper earthing wire, Al/PET tape
- 6
Outer jacket
UV resistant PVC outer jacket. RAL 6018 (Green)
Technical data
The numbers behind it.
Electrical · 0.60 mm
- Conductor diameter
- 0.60 mm
- Conductor resistance (20 °C)
- 130.0 Ω/km
- Insulation resistance (@500V DC)
- 100 MΩ/km
- Mutual capacitance
- 100 nF/km
- Operating voltage
- 300 V DC
- Test voltage (@ 1 minute)
- 800 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 10xD mm
- Temperature range operating
- -30°C ~ +70°C
Standards
Flame retardancy test
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2
From the Camcom datasheet. The datasheet for the chosen part number is the reference.