Building management system cable
1-Pair 14AWG Shielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
14 (19x27) Tinned Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polyethylene
- 4
Insulation thickness
0.8 mm (0.031 in)
- 5
Insulation diameter
3.55 mm (0.140 in)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape, 100% coverage
- 7
Drain wire
16 AWG (19x29) TC
- 8
Outer jacket
Low Smoke Zero Halogen (Flame Retardant)
- 9
Jacket thickness
0.9 mm (0.035 in)
- 10
Cable diameter
9.0 mm (0.35 in)
Technical data
The numbers behind it.
Electrical · 3751FS
- Conductor DCR
- 9.3 Ohm/km (2.8 Ohm/1000ft)
- Capacitance Cond-to-Cond
- 78 pF/m (24 pF/ft)
- Capacitance Cond-to-Other
- 154 pF/m (46.9 pF/ft)
- Characteristic impedance
- 58 Ohm
- Max current
- 9.5 Amps per Conductor at 25°C
- Voltage rating
- 600 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -45°C to +80°C
- Min. bending radius
- 45 mm (1.8 in) stationary, 90 mm (3.5 in) installation
- Max. pull tension
- 210 N (47 lbf)
- Approx. weight
- 103 kg/km (69.2 lbs/1000ft)
Color & Package
- Jacket
- LSZH
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.