Product image follows. Illustration for reference only.

Building management system cable

1 PAIR 22AWG Shielded RS-485 Communication Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Foil screened

Version

Camcom part no.

2361FS

2361FS · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Ten layers, from copper out.

  1. 1

    Conductor

    22 AWG (7x30) Tinned Copper

  2. 2

    No. of conductors

    2 (1 pairs)

  3. 3

    Insulation

    Polyethylene (Foam)

  4. 4

    Insulation thickness

    0.029 in (0.74 mm)

  5. 5

    Insulation diameter

    0.087 in (2.2 mm)

  6. 6

    Shield

    Bi-Laminate (Alum+Poly) Tape 100% + Tinned Copper Braid 65%

  7. 7

    Drain wire

    22 AWG (7x30) TC

  8. 8

    Outer jacket

    Polyvinyl Chloride

  9. 9

    Jacket thickness

    0.047 in (1.2 mm)

  10. 10

    Cable diameter

    0.294 in (7.47 mm)

Technical data

The numbers behind it.

Electrical · 2361FS

Conductor DCR
18.2 Ohm/1000ft
Capacitance Cond-to-Cond
11 pF/ft (36 pF/m)
Characteristic impedance
120 Ohm
Velocity of propagation
78%
Max current
6 Amps per Conductor at 30ºC
Insertion loss @ 1 MHz
0.5 dB/100ft
Voltage rating
300 V

Mechanical

Operating temperature
-20°C to +60°C
Min. bending radius
3.372 in (85.65 mm)
Max. pull tension
53.34 lbs (24.19 kg)
Approx. weight
43 lbs/1000ft

Color & Package

Jacket
Polyvinyl Chloride
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
2361FS2361FSPDF ↓