Building management system cable
1 PAIR 22AWG Shielded RS-485 Communication Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 AWG (7x30) Tinned Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polyethylene (Foam)
- 4
Insulation thickness
0.029 in (0.74 mm)
- 5
Insulation diameter
0.087 in (2.2 mm)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape 100% + Tinned Copper Braid 65%
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.047 in (1.2 mm)
- 10
Cable diameter
0.294 in (7.47 mm)
Technical data
The numbers behind it.
Electrical · 2361FS
- Conductor DCR
- 18.2 Ohm/1000ft
- Capacitance Cond-to-Cond
- 11 pF/ft (36 pF/m)
- Characteristic impedance
- 120 Ohm
- Velocity of propagation
- 78%
- Max current
- 6 Amps per Conductor at 30ºC
- Insertion loss @ 1 MHz
- 0.5 dB/100ft
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +60°C
- Min. bending radius
- 3.372 in (85.65 mm)
- Max. pull tension
- 53.34 lbs (24.19 kg)
- Approx. weight
- 43 lbs/1000ft
Color & Package
- Jacket
- Polyvinyl Chloride
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.