Building management system cable
1-Pair with 18AWG Unshielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Unshielded
Construction
Nine layers, from copper out.
- 1
Conductor
18 (16x30) Tinned Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polyvinyl Chloride
- 4
Insulation thickness
0.013 in (0.33 mm)
- 5
Insulation diameter
0.073 in (1.9 mm)
- 6
Shield
Unshielded
- 7
Outer jacket
Polyvinyl Chloride
- 8
Jacket thickness
0.032 in (0.81 mm)
- 9
Cable diameter
0.210 in (5.33 mm)
Technical data
The numbers behind it.
Electrical · 2551UN
- Conductor DCR
- 6.86 Ohm/1000ft
- Capacitance
- 25.5 pF/ft (83.7 pF/m)
- Max current
- 4.8 Amps per Conductor at 20ºC
- Voltage rating
- 300 V, 300 V (UL AWM 2464)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +80°C
- Min. bending radius
- 2.1 in (53 mm)
- Max. pull tension
- 42 lbs (19 kg)
- Approx. weight
- 21 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.