Building management system cable
1-Pair with 20AWG Shielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
20 AWG (7x28) Tinned Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polyethylene
- 4
Insulation thickness
0.016 in (0.41 mm)
- 5
Insulation diameter
1.78 mm (0.0701 in)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape, 100% coverage
- 7
Drain wire
20 AWG (7x28) TC
- 8
Outer jacket
Low Smoke Zero Halogen (Flame Retardant)
- 9
Jacket thickness
0.9 mm (0.035 in)
- 10
Cable diameter
5.4 mm (0.21 in)
Technical data
The numbers behind it.
Electrical · 3451FS
- Conductor DCR
- 31.2 Ohm/km (9.51 Ohm/1000ft)
- Capacitance Cond-to-Cond
- 88.6 pF/m (27.0 pF/ft)
- Capacitance Cond-to-Other
- 160.8 pF/m (49.01 pF/ft)
- Characteristic impedance
- 56 Ohm
- Inductance
- 0.59 µH/m (0.18 µH/ft)
- Velocity of propagation
- 66%
- Max current
- 3.9 Amps per Conductor
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -45°C To +80°C
- Min. bending radius
- 27 mm (1.1 in) stationary, 54 mm (2.1 in) installation
- Max. pull tension
- 210 N (47 lbf)
- Approx. weight
- 40.1 kg/km (26.9 lbs/1000ft)
Color & Package
- Jacket
- LSZH
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.