Building management system cable
10C 22AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 (7x30) Bare Copper
- 2
No. of conductors
10
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.008 in (0.20 mm)
- 5
Insulation diameter
0.062 in (1.6 mm)
- 6
Shield
Tape, Bi-Laminate (Alum+Poly), 100%
- 7
Drain wire
24 AWG (7x32) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.018 in (0.46 mm)
- 10
Cable diameter
0.217 in (5.51 mm)
Technical data
The numbers behind it.
Electrical · 2310FS
- Nom. conductor DCR
- 17.41 Ohm/1000ft
- Nom. capacitance Cond-to-Cond
- 22.5 pF/ft (73.8 pF/m)
- Nom. capacitance Cond-to-Other
- 40.5 pF/ft (133 pF/m)
- Nom. inductance
- 0.18 µH/ft (0.59 µH/m)
- Max. current
- 2 Amps per Conductor at 25ºC
- Nom outer shield DCR
- 14.41 Ohm/1000ft (47.28 Ohm/km)
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C To +75°C
- Min. bending radius
- 2.17 in (55.1 mm)
- Max. pull tension
- 96.5 lbs (43.8 kg)
- Approx. weight
- 32 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.