Building management system cable
1PAIR 22AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 AWG (7x30) Tinned Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polyethylene
- 4
Insulation thickness
0.017 in (0.43 mm)
- 5
Insulation diameter
0.062 in (1.6 mm)
- 6
Shield
Tape, Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.025 in (0.64 mm)
- 10
Cable diameter
0.175 in (4.45 mm)
Technical data
The numbers behind it.
Electrical · 2351FS
- Conductor DCR
- 18.2 Ohm/1000ft
- Capacitance Cond-to-Cond
- 24 pF/ft (79 pF/m)
- Capacitance Cond-to-Other
- 47 pF/ft (150 pF/m)
- Characteristic impedance
- 64 Ohm
- Inductance
- 0.2 µH/ft (0.66 µH/m)
- Max current
- 6 Amps per Conductor at 30ºC
- Voltage rating
- 300 V, 300 V (UL AWM 2092)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +60°C
- Min. bending radius
- 1.8 in (46 mm)
- Max. pull tension
- 27.3 lbs (12.4 kg)
- Approx. weight
- 16 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.