Building management system cable
2-Pair with 22AWG individual pair shielding PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Individually screened
Technical data
The numbers behind it.
Electrical · 2352IS
- High voltage test (KV)
- 800
- Conductor DCR @ 20 ℃
- ≤64.8 ohm/km
- Rated voltage
- 300 V
Values for this size are in its datasheet.
Mechanical
- Test object
- Jacket
- Test material
- PVC
- Before tensile strength (Mpa)
- ≥10.0
- Aging elongation
- ≥150 %
- Aging condition ( ℃ Xhrs)
- 80x168
- After tensile strength (Mpa)
- ≥80% unaged
- Aging elongation (%)
- ≥80% unaged
- Cold bend (-15 ℃ X4hrs)
- No crack
Standards
EN 60228
EN 50290-23
EN 50290-22
RoHS Directives
Construction
- Center conductor
- Tinned Copper
- Diameter
- 7/0.235 mm
- AWG
- 22
- Insulation
- PE
- Nom. thickness
- 0.20 mm
- Min. thickness
- 0.10 mm
- Insulation diameter
- 1.10±0.10 mm
- Individual shield
- Al-foil
- Coverage
- 100 %
- Drain wire
- Tinned Copper
- Structure
- 7/0.5 mm
- Jacket
- Fr-PVC
- Nom. thickness
- 0.60 mm
- Min. thickness
- 0.41 mm
- Cable diameter
- 5.50±0.30 mm
Application
- Low voltage analog signals, low voltage digital control
- line level audio; computer communication
- panel wiring
Color
- Jacket color
- Grey
Package
- 305m /Reel
- Box: 300x100x180mm
- N.W.: 9.40 KGS
- G.W.: 10.40 KGS
- Stack: 6
From the Camcom datasheet. The datasheet for the chosen part number is the reference.