Product image follows. Illustration for reference only.

Building management system cable

2-Pair with 22AWG individual shielding pair LSZH Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Individually screened

Version

Camcom part no.

3352IS

3352IS · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Ten layers, from copper out.

  1. 1

    Conductor

    22 (7x30) Tinned Copper

  2. 2

    No. of conductors

    4 (2 pairs)

  3. 3

    Insulation

    Polypropylene

  4. 4

    Insulation thickness

    0.0461 in [1.17 mm]

  5. 5

    Insulation diameter

    1.17 mm (0.0461 in)

  6. 6

    Shield

    Bi-Laminate (Alum+Poly) Tape, 100% coverage

  7. 7

    Drain wire

    24 AWG (7x32) TC

  8. 8

    Outer jacket

    Low Smoke Zero Halogen (Flame Retardant)

  9. 9

    Jacket thickness

    0.026 in [0.65 mm]

  10. 10

    Cable diameter

    4.55 mm (0.179 in)

Technical data

The numbers behind it.

Electrical · 3352IS

Conductor DCR
49.2 Ohm/km (15.0 Ohm/1000ft)
Inner shield DCR
54.5 Ohm/km (16.6 Ohm/1000ft)
Capacitance Cond-to-Cond
115 pF/m (35.1 pF/ft)
Capacitance Cond-to-Other
203 pF/m (61.9 pF/ft)
Characteristic impedance
45 Ohm
Inductance
056 µH/m (17 µH/ft)
Max current
2.3 Amps per Conductor
Voltage rating
300 V

Mechanical

Operating temperature
-45°C To +80°C
Min. bending radius
45.5 mm (1.79 in)
Max. pull tension
226 N (50.8 lbf)
Approx. weight
24 lbs/1000ft [36 kg/km]

Color & Package

Jacket
LSZH
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
3352IS3352ISPDF ↓