Building management system cable
2C 10AWG Unshielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Unshielded
Construction
Nine layers, from copper out.
- 1
Conductor
10 AWG (65x28) Bare Copper
- 2
No. of conductors
2
- 3
Insulation
Polyvinyl Chloride
- 4
Insulation thickness
0.020 in (0.51 mm)
- 5
Insulation diameter
0.152 in (3.86 mm)
- 6
Shield
Unshielded
- 7
Outer jacket
Polyvinyl Chloride
- 8
Jacket thickness
0.026 in (0.66 mm)
- 9
Cable diameter
0.356 in (9.04 mm)
Technical data
The numbers behind it.
Electrical · 2902UN
- Nom. conductor DCR
- 1.03 Ohm/1000ft (3.38 Ohm/km)
- Nom. capacitance Cond-to-Cond
- 26 pF/ft (85 pF/m)
- Nom. inductance
- 0.15 µH/ft (0.49 µH/m)
- Max. current
- 27.8 Amps per conductor @ 25°C
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +75°C
- Min. bending radius
- 3.6 in (91 mm)
- Max. pull tension
- 260 lbs (120 kg)
- Approx. weight
- 91 lbs/1000ft (140 kg/km)
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.