Product image follows. Illustration for reference only.

Building management system cable

2C 12AWG Shielded FPLR Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Foil screened

Version

Camcom part no.

4802FS

4802FS · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Ten layers, from copper out.

  1. 1

    Conductor

    12 (Solid) Bare Copper

  2. 2

    No. of conductors

    2

  3. 3

    Insulation

    Polypropylene

  4. 4

    Insulation thickness

    0.01 in (0.25 mm)

  5. 5

    Insulation diameter

    0.105 in (2.67 mm)

  6. 6

    Shield

    Bi-Laminate (Alum+Poly) Tape, 100% coverage

  7. 7

    Drain wire

    20 AWG (7x28) TC

  8. 8

    Outer jacket

    Polyvinyl Chloride

  9. 9

    Jacket thickness

    0.017 in (0.43 mm)

  10. 10

    Cable diameter

    0.243 in

Technical data

The numbers behind it.

Electrical · 4802FS

Nom. conductor DCR
1.65 Ohm/1000ft
Nom. capacitance Cond-to-Cond
71 pF/ft (230 pF/m)
Nom. capacitance Cond-to-Other
128 pF/ft (420 pF/m)
Nom. inductance
0.14 µH/ft (0.46 µH/m)
Max. current
12 Amps per Conductor at 25ºC
Voltage rating
300 V

Mechanical

Operating temperature
-20°C To +75°C
Min. bending radius
3.64 in (92.5 mm)
Max. pull tension
170 lbs (77 kg)
Approx. weight
55 lbs/1000ft

Color & Package

Jacket
Polyvinyl Chloride
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
4802FS4802FSPDF ↓