Building management system cable
2C 12AWG Shielded FPLR Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
12 (Solid) Bare Copper
- 2
No. of conductors
2
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.01 in (0.25 mm)
- 5
Insulation diameter
0.105 in (2.67 mm)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape, 100% coverage
- 7
Drain wire
20 AWG (7x28) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.017 in (0.43 mm)
- 10
Cable diameter
0.243 in
Technical data
The numbers behind it.
Electrical · 4802FS
- Nom. conductor DCR
- 1.65 Ohm/1000ft
- Nom. capacitance Cond-to-Cond
- 71 pF/ft (230 pF/m)
- Nom. capacitance Cond-to-Other
- 128 pF/ft (420 pF/m)
- Nom. inductance
- 0.14 µH/ft (0.46 µH/m)
- Max. current
- 12 Amps per Conductor at 25ºC
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C To +75°C
- Min. bending radius
- 3.64 in (92.5 mm)
- Max. pull tension
- 170 lbs (77 kg)
- Approx. weight
- 55 lbs/1000ft
Color & Package
- Jacket
- Polyvinyl Chloride
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.