Building management system cable
2C 12AWG Unshielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Unshielded
Technical data
The numbers behind it.
Electrical · 3802UN
- Conductor DCR @ 20 ℃
- ≤5.56 ohm/km
- Max. operating voltage
- 300 V
- Dielectric strength
- 1.0 kV/min
Values for this size are in its datasheet.
Mechanical
- Test object
- Jacket
- Test material
- LSZH
- Before tensile strength (Mpa)
- ≥9.0
- Aging elongation
- ≥125 %
- Aging condition ( ℃ Xhrs)
- 100x168
- After tensile strength (Mpa)
- ±40%
- Aging elongation
- ±30%
- Cold bend (-15 ℃ X4hrs)
- No Cracks
- Rated temperature
- 70 ℃
Standards
EN 50290-2-23
EN 50290-2-27
IEC60332-1
RoHS Directives
Construction
- Conductor: Strand Bare Copper
- AWG: 12
- Diameter: 65/0.254 mm
- Insulation: PE
- Nom. thickness: 0.35 mm
- Min. thickness: 0.25 mm
- Insulation diameter: 3.10±0.10 mm
- Cabling: 2 Cores
- Rip cord: Yes
- Jacket: LSZH
- Nom. thickness: 0.65 mm
- Min. thickness: 0.45 mm
- Cable Diameter (mm) 7.50±0.30
Application
- For Security & Alarm System
- Analog Audio Transmission
- Not for main power Line
Color
- Jacket color
- Grey
Package
- 305m /Reel
- Box: 360x130x230mm
- N.W.: 28.40kgs
- G.W.: 29.40kgs
- Stack: 6
From the Camcom datasheet. The datasheet for the chosen part number is the reference.