Building management system cable
2C 14AWG Shielded FPLR Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
14 AWG (19x27) Bare Copper
- 2
No. of conductors
2 (1 pairs)
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.011 in (0.28 mm)
- 5
Insulation diameter
0.092 in (2.3 mm)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.017 in (0.43 mm)
- 10
Cable diameter
0.222 in
Technical data
The numbers behind it.
Electrical · 4702FS
- Conductor DCR
- 2.72 Ohm/1000ft
- Capacitance Cond-to-Cond
- 29.5 pF/ft (96.8 pF/m)
- Capacitance Cond-to-Other
- 53.1 pF/ft (174 pF/m)
- Max. current
- 8 Amps per Conductor at 25°C
- Shield DCR
- 11.5 Ohm/1000ft (37.7 Ohm/km)
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +75°C
- Min. bending radius
- 3.3 in (84 mm)
- Max. pull tension
- 108 lbs (49.0 kg)
- Approx. weight
- 37 lbs/1000ft
Color & Package
- Jacket
- Polyvinyl Chloride
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.