Product image follows. Illustration for reference only.

Building management system cable

2C 14AWG Shielded FPLR Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Foil screened

Version

Camcom part no.

4702FS

4702FS · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Ten layers, from copper out.

  1. 1

    Conductor

    14 AWG (19x27) Bare Copper

  2. 2

    No. of conductors

    2 (1 pairs)

  3. 3

    Insulation

    Polypropylene

  4. 4

    Insulation thickness

    0.011 in (0.28 mm)

  5. 5

    Insulation diameter

    0.092 in (2.3 mm)

  6. 6

    Shield

    Tape - Bi-Laminate (Alum+Poly), 100% coverage

  7. 7

    Drain wire

    22 AWG (7x30) TC

  8. 8

    Outer jacket

    Polyvinyl Chloride

  9. 9

    Jacket thickness

    0.017 in (0.43 mm)

  10. 10

    Cable diameter

    0.222 in

Technical data

The numbers behind it.

Electrical · 4702FS

Conductor DCR
2.72 Ohm/1000ft
Capacitance Cond-to-Cond
29.5 pF/ft (96.8 pF/m)
Capacitance Cond-to-Other
53.1 pF/ft (174 pF/m)
Max. current
8 Amps per Conductor at 25°C
Shield DCR
11.5 Ohm/1000ft (37.7 Ohm/km)
Voltage rating
300 V

Mechanical

Operating temperature
-20°C to +75°C
Min. bending radius
3.3 in (84 mm)
Max. pull tension
108 lbs (49.0 kg)
Approx. weight
37 lbs/1000ft

Color & Package

Jacket
Polyvinyl Chloride
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
4702FS4702FSPDF ↓