Product image follows. Illustration for reference only.

Building management system cable

2C 14AWG Unshielded PVC Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Unshielded

Version

Camcom part no.

2702UN

2702UN · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Technical data

The numbers behind it.

Electrical · 2702UN

Conductor DCR @ 20 ℃
≤9.9 ohm/km
Max. operating voltage
300 V
Dielectric strength
1.0 kV/min

Mechanical

Test object
Jacket
Test material
PVC
Before tensile strength (Mpa)
≥10.0
Aging elongation
≥150 %
Aging condition ( ℃ Xhrs)
80x168
After tensile strength (Mpa)
≥80% unaged
Aging elongation (%)
≥80% unaged
Cold bend (-15 ℃ X4hrs)
No crack
Rated temperature
75 ℃

Standards

EN 50290-2-23

EN 50290-2-22

IEC60332-1

RoHS Directives

Construction

  • Conductor: Strand Bare Copper
  • AWG: 14
  • Diameter: 40/0.243 mm
  • Insulation: PE
  • Nom. thickness: 0.25 mm
  • Min. thickness: 0.15 mm
  • Insulation diameter: 2.30±0.10 mm
  • Cabling: 2 Cores
  • Rip cord: Yes
  • Jacket: Fr-PVC
  • Nom. thickness: 0.60 mm
  • Min. thickness: 0.41 mm
  • Cable Diameter (mm) 5.80±0.20

Application

  • For Security & Alarm System
  • Analog Audio Transmission
  • Not for main power Line

Color

Jacket color
Grey

Package

  • 305m /Reel
  • Box: 320x100x180mm
  • N.W.: 16.80kgs
  • G.W.: 17.80kgs
  • Stack: 6

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
2702UN2702UNPDF ↓