Building management system cable
3-Pair 24AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
24 AWG (7x32) Tinned Copper
- 2
No. of conductors
6 (3 pairs)
- 3
Insulation
Polyethylene
- 4
Insulation thickness
0.022 in (0.56 mm)
- 5
Insulation diameter
0.068 in (1.7 mm)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape 100% + Tinned Copper Braid 90%
- 7
Drain wire
24 AWG (7x32) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.035 in (0.89 mm)
- 10
Cable diameter
0.360 in (9.14 mm)
Technical data
The numbers behind it.
Electrical · 2253FS
- Conductor DCR
- 24 Ohm/1000ft
- Capacitance Cond-to-Cond
- 12.8 pF/ft (42.0 pF/m)
- Capacitance Cond-to-Other
- 23 pF/ft (75 pF/m)
- Characteristic impedance
- 120 Ohm
- Velocity of propagation
- 66%
- Max current
- 1.54 Amps per Conductor at 25ºC
- Insertion loss @ 1MHz
- 0.6 dB/100ft
- Voltage rating
- 300 V, 30 V (UL AWM 2919)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -30°C to +80°C
- Min. bending radius
- 3.75 in (95.3 mm)
- Max. pull tension
- 105.5 lbs (47.85 kg)
- Approx. weight
- 62 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.