Building management system cable
3-Pair with 22AWG individual pair shielding PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 AWG (7x30) Tinned Copper
- 2
No. of conductors
6 (3 pairs)
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.011 in (0.28 mm)
- 5
Insulation diameter
0.050 in (1.3 mm)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly), 100% coverage, each pair
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.034 in (0.86 mm)
- 10
Cable diameter
0.273 in (6.93 mm)
Technical data
The numbers behind it.
Electrical · 2353IS
- Conductor DCR
- 18.2 Ohm/1000ft
- Capacitance Cond-to-Cond
- 30 pF/ft (98 pF/m)
- Characteristic impedance
- 50 Ohm
- Velocity of propagation
- 66%
- Max. current
- 2.8 Amps per Conductor at 25ºC
- Voltage rating
- 300 V, 30 V (UL AWM 2919)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +80°C
- Min. bending radius
- 2.7 in (69 mm)
- Max. pull tension
- 63.7 lbs (28.9 kg)
- Approx. weight
- 39 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.