Product image follows. Illustration for reference only.

Building management system cable

3C 16AWG Unshielded PVC Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Unshielded

Version

Camcom part no.

2603UN

2603UN · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Nine layers, from copper out.

  1. 1

    Conductor

    16 AWG (19x29) Bare Copper

  2. 2

    No. of conductors

    3

  3. 3

    Insulation

    Polyolefin

  4. 4

    Insulation thickness

    0.008 in (0.20 mm)

  5. 5

    Insulation diameter

    0.073 in (1.9 mm)

  6. 6

    Shield

    Unshielded

  7. 7

    Outer jacket

    Polyvinyl Chloride

  8. 8

    Jacket thickness

    0.017 in (0.43 mm)

  9. 9

    Cable diameter

    0.191 in (4.85 mm)

Technical data

The numbers behind it.

Electrical · 2603UN

Conductor DCR
4.2 Ohm/1000ft (14 Ohm/km)
Capacitance Cond-to-Cond
23.5 pF/ft (77.1 pF/m)
Max. current
6.25 Amps per conductor @ 25°C
Voltage rating
300 V

Mechanical

Operating temperature
-20°C to +75°C
Min. bending radius
1.9 in (48 mm)
Max. pull tension
88 lbs (40 kg)
Approx. weight
32 lbs/1000ft (48 kg/km)

Color & Package

Jacket
PVC
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
2603UN2603UNPDF ↓