Building management system cable
4 PAIR 22AWG braided shield RS-485 cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 (7x30) Tinned Copper
- 2
No. of conductors
8 (4 pairs)
- 3
Insulation
Polyolefin (PO, HDPE, PP) (Foam)
- 4
Insulation thickness
0.0025 in
- 5
Insulation diameter
0.03 in
- 6
Shield
Alum / Poly® (100%) + TC Braid (65%)
- 7
Drain wire
Tinned Copper, 0.03 mm, 22 AWG, 7x30
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.053 in
- 10
Cable diameter
0.448 in
Technical data
The numbers behind it.
Electrical · 2364BS
- Conductor DCR
- 14.7 Ohm/1000ft
- Shield DCR
- 2.53 Ohm/1000ft
- Capacitance C-to-C
- 11 pF/ft
- Capacitance C-to-Shield
- 20.9 pF/ft
- Inductance
- 0.225 µH/ft
- Characteristic impedance
- 120 Ohm
- Insertion loss
- 0.5 dB/100ft @ 1MHz
- Velocity of propagation
- 78%
- Max current
- 2.7 A/conductor @ 25°C
- Voltage rating
- 300 V RMS
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +60°C
- Min. bending radius
- 5.5 in
- Max. pull tension
- 100 lbs
- Approx. weight
- 96.4 lbs/1000ft
Color & Package
- Jacket
- Polyvinyl Chloride
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.