Building management system cable
4C 16AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
16 AWG (19x29) Bare Copper
- 2
No. of conductors
4
- 3
Insulation
Polyolefin
- 4
Insulation thickness
0.008 in (0.20 mm)
- 5
Insulation diameter
0.073 in (1.9 mm)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
24 AWG (7x32) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.017 in (0.43 mm)
- 10
Cable diameter
0.214 in (5.44 mm)
Technical data
The numbers behind it.
Electrical · 2604FS
- Conductor DCR
- 4 Ohm/1000ft
- Capacitance Cond-to-Cond
- 30.5 pF/ft (100 pF/m)
- Capacitance Cond-to-Other
- 55 pF/ft (180 pF/m)
- Max current
- 5.0 Amps per conductor @ 25°C
- Shield DCR
- 14.4 Ohm/1000ft (47.2 Ohm/km)
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +75°C
- Min. bending radius
- 2.1 in (53 mm)
- Max. pull tension
- 146 lbs (66.2 kg)
- Approx. weight
- 44 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.