Building management system cable
4C 16AWG Un-Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Unshielded
Construction
Nine layers, from copper out.
- 1
Conductor
16 AWG (19x29) Bare Copper
- 2
No. of conductors
4
- 3
Insulation
Polyolefin
- 4
Insulation thickness
0.008 in (0.20 mm)
- 5
Insulation diameter
0.073 in (1.9 mm)
- 6
Shield
Unshielded
- 7
Outer jacket
Polyvinyl Chloride
- 8
Jacket thickness
0.017 in (0.43 mm)
- 9
Cable diameter
0.210 in (5.33 mm)
Technical data
The numbers behind it.
Electrical · 2604UN
- Conductor DCR
- 4.2 Ohm/1000ft
- Capacitance
- 23 pF/ft (75 pF/m)
- Max current
- 5.0 Amps per conductor @ 25°C
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +75°C
- Min. bending radius
- 2.1 in (53 mm)
- Max. pull tension
- 117 lbs (53.1 kg)
- Approx. weight
- 42 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.