Building management system cable
4C 18AWG Shielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
18 AWG (7x26) Bare Copper
- 2
No. of conductors
4
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.2 mm (0.0079 in)
- 5
Insulation diameter
1.5 mm (0.059 in)
- 6
Shield
Bi-Laminate (Alum+Poly) Tape, 100% coverage
- 7
Drain wire
24 AWG (7x32) TC
- 8
Outer jacket
Low Smoke Zero Halogen (Flame Retardant)
- 9
Jacket thickness
0.4 mm (0.016 in)
- 10
Cable diameter
4.8 mm (0.19 in)
Technical data
The numbers behind it.
Electrical · 3504FS
- Conductor DCR
- 21.3 Ohm/km (6.49 Ohm/1000ft)
- Capacitance Cond-to-Cond
- 70 pF/m (21 pF/ft)
- Capacitance Cond-to-Other
- 150 pF/m (46 pF/ft)
- Max current
- 4 Amps per Conductor
- Shield DCR
- 23.6 Ohm/km (7.19 Ohm/1000ft)
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C To +70°C
- Min. bending radius
- 24 mm (0.94 in) stationary, 48 mm (1.9 in) installation
- Max. pull tension
- 170 N (38 lbf)
Color & Package
- Jacket
- LSZH
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.