Product image follows. Illustration for reference only.

Building management system cable

4C 20AWG Shielded PVC Cable

Available as 1 part number. Full construction and technical data are in the datasheet.

Foil screened

Version

Camcom part no.

2404FS

2404FS · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Ten layers, from copper out.

  1. 1

    Conductor

    20 AWG (7x28) Bare Copper

  2. 2

    No. of conductors

    4

  3. 3

    Insulation

    Polypropylene

  4. 4

    Insulation thickness

    0.008 in (0.20 mm)

  5. 5

    Insulation diameter

    0.052 in (1.3 mm)

  6. 6

    Shield

    Bi-Laminate (Alum+Poly) Tape, 100% coverage

  7. 7

    Drain wire

    24 AWG (7x32) TC

  8. 8

    Outer jacket

    Polyvinyl Chloride

  9. 9

    Jacket thickness

    0.017 in (0.43 mm)

  10. 10

    Cable diameter

    0.163 in (4.14 mm)

Technical data

The numbers behind it.

Electrical · 2404FS

Conductor DCR
10.2 Ohm/1000ft
Capacitance Cond-to-Cond
24.75 pF/ft (81.20 pF/m)
Capacitance Cond-to-Other
44.5 pF/ft (146 pF/m)
Max. current
6.4 Amps per conductor @ 25°C
Shield DCR
11.3 Ohm/1000ft (37.1 Ohm/km)
Voltage rating
300 V

Mechanical

Operating temperature
-20°C to +75°C
Min. bending radius
1.6 in (41 mm)
Max. pull tension
56 lbs (25 kg)
Approx. weight
22 lbs/1000ft

Color & Package

Jacket
PVC
Packing
305 m / 500 m reels or drums

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

One part number.

Camcom part no.VersionDatasheet
2404FS2404FSPDF ↓