Building management system cable
5-Pair 22AWG individual pair shielding PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 AWG (7x30) Tinned Copper
- 2
No. of conductors
10 (5 pairs)
- 3
Insulation
SR-Polyvinyl Chloride (Semi-Rigid)
- 4
Insulation thickness
0.011 in (0.28 mm)
- 5
Insulation diameter
0.051 in (1.3 mm)
- 6
Shield
Bi-Laminate (Alum+Poly) tape 100% + Tinned Copper braid 65%
- 7
Drain wire
Tinned Copper braid
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.035 in (0.89 mm)
- 10
Cable diameter
0.322 in (8.18 mm)
Technical data
The numbers behind it.
Electrical · 2355IS
- Conductor DCR
- 18.2 Ohm/1000ft
- Capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
- Capacitance Cond-to-Other
- 63 pF/ft (210 pF/m)
- Velocity of Prop.
- 60%
- Max. current
- 2.2 Amps per Conductor at 25ºC
- Outer shield DCR
- 6.8 Ohm/1000ft (22 Ohm/km)
- Voltage rating
- 300 V, 300 V (UL AWM 2464)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -30°C to +80°C
- Min. bending radius
- 3.2 in (81 mm)
- Max. pull tension
- 91 lbs (41 kg)
- Approx. weight
- 63 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.