Building management system cable
6-Pair 22AWG Shielded PVC Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Ten layers, from copper out.
- 1
Conductor
22 AWG (Solid) Tinned Copper
- 2
No. of conductors
12 (6 pairs)
- 3
Insulation
Polyvinyl Chloride
- 4
Insulation thickness
0.013 in (0.33 mm)
- 5
Insulation diameter
0.052 in (1.3 mm)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
22 AWG (7x30) TC
- 8
Outer jacket
Polyvinyl Chloride
- 9
Jacket thickness
0.032 in (0.81 mm)
- 10
Cable diameter
0.315 in
Technical data
The numbers behind it.
Electrical · 2356FS
- Nom. conductor DCR
- 20.6 Ohm/1000ft
- Nom. capacitance Cond-to-Cond
- 35 pF/ft (110 pF/m)
- Nom. capacitance Cond-to-Other
- 50 pF/ft (160 pF/m)
- Nom. inductance
- 0.2 µH/ft (0.66 µH/m)
- Max. current
- 4.2 Amps per Conductor at 30ºC
- Nom outer shield DCR
- 11.5 Ohm/1000ft (37.7 Ohm/km)
- Voltage rating
- 300 V
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +80°C
- Min. bending radius
- 3.15 in (80.0 mm) stationary / 3.15 in installation
- Max. pull tension
- 102 lbs (46.3 kg)
- Approx. weight
- 57 lbs/1000ft
Color & Package
- Jacket
- PVC
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.