Building management system cable
6C 16AWG Shielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Construction
Nine layers, from copper out.
- 1
Conductor
16 (19x29) Bare Copper
- 2
No. of conductors
6
- 3
Insulation
Polypropylene
- 4
Insulation thickness
0.2 mm (0.0079 in)
- 5
Insulation diameter
1.8 mm (0.071 in)
- 6
Shield
Tape - Bi-Laminate (Alum+Poly) 100% coverage
- 7
Outer jacket
Low Smoke Zero Halogen (Flame Retardant)
- 8
Jacket thickness
0.4 mm (0.016 in)
- 9
Cable diameter
6.90 mm (0.272 in)
Technical data
The numbers behind it.
Electrical · 3606FS
- Nom. conductor DCR
- 13.1 Ohm/km (3.99 Ohm/1000ft)
- Nom. capacitance Cond-to-Cond
- 120 pF/m (37 pF/ft)
- Nom. capacitance Cond-to-Other
- 220 pF/m (67 pF/ft)
- Nom outer shield DCR
- 15.4 Ohm/km (4.69 Ohm/1000ft)
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C To +70°C
- Min. bending radius
- 70 mm (2.8 in)
- Max. pull tension
- 360 N (81 lbf)
Color & Package
- Jacket
- LSZH
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.