Building management system cable
8C 20AWG Shielded LSZH Cable
Available as 1 part number. Full construction and technical data are in the datasheet.
Foil screened
Construction
Ten layers, from copper out.
- 1
Conductor
20 AWG (7x28) Bare Copper
- 2
No. of conductors
8
- 3
Insulation
Polyolefin
- 4
Insulation thickness
0.2 mm
- 5
Insulation diameter
1.25 mm
- 6
Shield
Bi-Laminate (Alum+Poly), 100% coverage
- 7
Drain wire
24 AWG (7x32) TC
- 8
Outer jacket
Low Smoke Zero Halogen (Flame Retardant)
- 9
Jacket thickness
0.5 mm
- 10
Cable diameter
5.60 mm
Technical data
The numbers behind it.
Electrical · 3408FS
- Nom. conductor DCR
- 34 Ohm/km
- Nom. capacitance Cond-to-Cond
- 110 pF/m
- Nom. capacitance Cond-to-Other
- 224 pF/m
- Max. current
- 2.7 Amps per Conductor
- Nom outer shield DCR
- 24 Ohm/km
Values for this size are in its datasheet.
Mechanical
- Operating temperature
- -20°C to +70°C
- Min. bending radius
- 5*D/10*D
- Max. pull tension
- 200 N
Color & Package
- Jacket
- LSZH
- Packing
- 305 m / 500 m reels or drums
From the Camcom datasheet. The datasheet for the chosen part number is the reference.