Fire resistant cable
JE-H(St)H…Bd FE180 / E30-E60-E90 / PH120
Available as 8 part numbers from 1 x 2 x 0.8 mm to 10 x 2 x 0.8 mm. Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
539851FSD
1 x 2 x 0.8 mm · 1,000 m
Stock and lead time: ask us by email.
Construction
Six layers, from copper out.

- 1
Conductor
Class 1 electrolytic solid copper (IEC 60228, DIN VDE 0295, EN 60228)
- 2
Insulation
Cross-linked polymer compound in ceramic form (VDE 0815)
- 3
Stranding
Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers.
- 4
Wrapping
Polyester tape, glass yarn tape
- 5
Screen
Tinned copper earthing wire, Al/PET tape
- 6
Outer jacket
UV resistant halogen-free outer jacket. RAL 2008 (Orange)
Technical data
The numbers behind it.
Electrical · 1 x 2 x 0.8 mm
- Conductor diameter
- 0.80 mm
- Conductor resistance (20 °C)
- 73.2 Ω/km
- Insulation resistance (@500V DC)
- 100 MΩ/km
- Mutual capacitance
- 100 nF/km
- Operating voltage
- 300 V DC
- Test voltage (@ 1 minute)
- 1000 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 10xD mm
- Temperature range operating
- -40°C ~ +70°C
Standards
Circuit integrity test (FE180)
IEC 60331-21
Circuit integrity with shock test
EN 50200, VDE 0482-200,
(PH120) BS EN 50200
Cable system circuit integrity test (E30
DIN 4102-12 E30 / E60 /
E60 / E90) E90
From the Camcom datasheet. The datasheet for the chosen part number is the reference.
Cable type data