Fire resistant cable
LIHCHSWAH-TP FE180 PH120
Available as 5 part numbers from 0.50 mm² to 2.50 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
530550BSA
0.50 mm² · 1,000 m
Stock and lead time: ask us by email.
Construction
Eight layers, from copper out.

- 1
Conductor
Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)
- 2
Insulation
Cross-linked polymer compound in ceramic form (DIN 47100)
- 3
Stranding
Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers.
- 4
Wrapping
Polyester tape, glass yarn tape
- 5
Screen
Tinned copper braiding
- 6
Inner jacket
UV resistant halogen-free inner jacket.
- 7
Armor
Galvanized steel wire armor
- 8
Outer jacket
UV resistant halogen-free outer jacket.
Technical data
The numbers behind it.
Electrical · 0.50 mm²
- Conductor diameter
- 0.50 mm²
- Conductor resistance (20 °C)
- 39.0 Ω/km
- Insulation resistance (@500V DC)
- 100 MΩ/km
- Mutual capacitance
- 100 nF/km
- Operating voltage
- 300 V DC
- Test voltage (@ 1 minute)
- 2000 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 10xD mm
- Temperature range operating
- -40°C ~ +70°C
Standards
Circuit integrity test (FE180)
IEC 60331-21
Circuit integrity with shock test
EN 50200, VDE 0482-200,
(PH120) BS EN 50200
From the Camcom datasheet. The datasheet for the chosen part number is the reference.