LIHCHSWAH-TP FE180 PH120 cable, stripped back to show its construction

Fire resistant cable

LIHCHSWAH-TP FE180 PH120

Available as 5 part numbers from 0.50 mm² to 2.50 mm². Full construction and technical data are in the datasheet.

Braid screened

Conductor size

Camcom part no.

530550BSA

0.50 mm² · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Eight layers, from copper out.

Cross-section of LIHCHSWAH-TP FE180 PH120
  1. 1

    Conductor

    Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)

  2. 2

    Insulation

    Cross-linked polymer compound in ceramic form (DIN 47100)

  3. 3

    Stranding

    Insulations are stranded into pairs, four pairs are stranded together into groups, groups are stranded in layers.

  4. 4

    Wrapping

    Polyester tape, glass yarn tape

  5. 5

    Screen

    Tinned copper braiding

  6. 6

    Inner jacket

    UV resistant halogen-free inner jacket.

  7. 7

    Armor

    Galvanized steel wire armor

  8. 8

    Outer jacket

    UV resistant halogen-free outer jacket.

Technical data

The numbers behind it.

Electrical · 0.50 mm²

Conductor diameter
0.50 mm²
Conductor resistance (20 °C)
39.0 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Mutual capacitance
100 nF/km
Operating voltage
300 V DC
Test voltage (@ 1 minute)
2000 V DC

Mechanical

Bending radius
10xD mm
Temperature range operating
-40°C ~ +70°C

Standards

Circuit integrity test (FE180)

IEC 60331-21

Circuit integrity with shock test

EN 50200, VDE 0482-200,

(PH120) BS EN 50200

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
530550BSA0.50 mm²PDF ↓
530750BSA0.75 mm²PDF ↓
531050BSA1.00 mm²PDF ↓
531550BSA1.50 mm²PDF ↓
532550BSA2.50 mm²PDF ↓