LIHH FE180 PH120 cable, stripped back to show its construction

Fire resistant cable

LIHH FE180 PH120

Available as 95 part numbers from 2 x 0.5 mm² to 27 x 2.5 mm². Full construction and technical data are in the datasheet.

Unshielded

Conductor size

Camcom part no.

530502UN

2 x 0.5 mm² · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Five layers, from copper out.

Cross-section of LIHH FE180 PH120
  1. 1

    Conductor

    Stranded electrolytic copper conductor (Class 5) (IEC 60228, EN 60228, DIN VDE 0295)

  2. 2

    Insulation

    Cross-linked polymer compound in ceramic form (DIN 47100)

  3. 3

    Stranding

    In layers

  4. 4

    Wrapping

    Polyester tape, glass yarn tape

  5. 5

    Outer jacket

    UV resistant halogen-free outer jacket. RAL 2008 (Orange)

Technical data

The numbers behind it.

Electrical · 2 x 0.5 mm²

Conductor diameter
0.50 mm²
Conductor resistance (20 °C)
39.0 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Mutual capacitance
100 nF/km
Operating voltage
300 V DC
Test voltage (@ 1 minute)
2000 V DC

Mechanical

Bending radius
10xD mm
Temperature range operating
-40°C ~ +70°C

Standards

Circuit integrity test (FE180)

IEC 60331-21

Circuit integrity with shock test

EN 50200, VDE 0482-200,

(PH120) BS EN 50200

From the Camcom datasheet. The datasheet for the chosen part number is the reference.

Cable type data

Every size, one part number each.

Camcom part no.Conductor sizeDatasheet
530502UN2 x 0.5 mm²PDF ↓
530503UN3 x 0.5 mm²PDF ↓
530504UN4 x 0.5 mm²PDF ↓
530505UN5 x 0.5 mm²PDF ↓
530506UN6 x 0.5 mm²PDF ↓
530507UN7 x 0.5 mm²PDF ↓
530508UN8 x 0.5 mm²PDF ↓
530509UN9 x 0.5 mm²PDF ↓
530510UN10 x 0.5 mm²PDF ↓
530512UN12 x 0.5 mm²PDF ↓
530514UN14 x 0.5 mm²PDF ↓
530516UN16 x 0.5 mm²PDF ↓
530518UN18 x 0.5 mm²PDF ↓
530519UN19 x 0.5 mm²PDF ↓
530520UN20 x 0.5 mm²PDF ↓
530521UN21 x 0.5 mm²PDF ↓
530524UN24 x 0.5 mm²PDF ↓
530525UN25 x 0.5 mm²PDF ↓
530527UN27 x 0.5 mm²PDF ↓
530702UN2 x 0.75 mm²PDF ↓