RE-2G(St)H-TP&TT FE180 cable, stripped back to show its construction

Fire resistant cable

RE-2G(St)H-TP&TT FE180

Available as 5 part numbers from 0.50 mm² to 2.50 mm². Full construction and technical data are in the datasheet.

Foil screened

Conductor size

Camcom part no.

530550FSG

0.50 mm² · 1,000 m

Request a quote

Stock and lead time: ask us by email.

Construction

Six layers, from copper out.

Cross-section of RE-2G(St)H-TP&TT FE180
  1. 1

    Conductor

    Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)

  2. 2

    Insulation

    Cross-linked polymer compound in ceramic form

  3. 3

    Stranding

    Insulations are stranding into pairs or triads

  4. 4

    Wrapping

    Polyester tape, glass yarn tape

  5. 5

    Screen

    Tinned copper earthing wire, Al/PET tape

  6. 6

    Outer jacket

    UV resistant halogen-free outer jacket.

Technical data

The numbers behind it.

Electrical · 0.50 mm²

Conductor diameter
0.50 mm²
Conductor resistance (20 °C)
36.0 Ω/km
Insulation resistance (@500V DC)
100 MΩ/km
Operating voltage
300 V DC
Test voltage (@ 1 minute)
2000 V DC

Mechanical

Bending radius
10xD mm
Temperature range operating
-40°C ~ +70°C

Standards

Smoke density test

IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2

Corrosive gas test

IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3

Halogen-free test

IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1

Flame propagation test

IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24

Flame retardancy test

IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2

Fire resistance test (FE180)

IEC 60331-21