Fire resistant cable
RE-2X(St)H-PiMF&TiMF FE180
Available as 5 part numbers from 0.50 mm² to 2.50 mm². Full construction and technical data are in the datasheet.
Conductor size
Camcom part no.
530550ISX
0.50 mm² · 1,000 m
Stock and lead time: ask us by email.
Construction
Ten layers, from copper out.

- 1
Conductor
Stranded electrolytic copper conductor (Class 2) (IEC 60228, EN 60228, DIN VDE 0295)
- 2
Wrapping
Each conductor wrapped with mica tape
- 3
Insulation
XLPE (BS EN 50290-2, VDE 0207 YI1)
- 4
Individual stranding
Insulations are stranding into pairs or triads
- 5
Individual wrapping
Polyester tape
- 6
Individual screen
Tinned copper earthing wire, Al/PET tape
- 7
Overall stranding
Screened pairs or triads are stranding into layers
- 8
Overall wrapping
Polyester tape
- 9
Overall screen
Tinned copper earthing wire, Al/PET tape
- 10
Outer jacket
UV resistant halogen-free outer jacket.
Technical data
The numbers behind it.
Electrical · 0.50 mm²
- Conductor diameter
- 0.50 mm²
- Conductor resistance (20 °C)
- 36.0 Ω/km
- Insulation resistance (@500V DC)
- Min. 1000 MΩ/km
- Mutual capacitance
- Max. 250 nF/km
- Operating voltage
- 300 V DC
- Test voltage (@ 1 minute)
- 2000 V DC
Values for this size are in its datasheet.
Mechanical
- Bending radius
- 10xD mm
- Temperature range operating
- -30°C ~ +90°C
Standards
Smoke density test
IEC 61034-2, VDE 0482-1034-2, BS EN 61034-2
Corrosive gas test
IEC 60754-2, VDE 0482-267-2-3, BS EN 50267-2-3
Halogen-free test
IEC 60754-1, VDE 0482-267-2-1, BS EN 50267-2-1
Flame propagation test
IEC 60332-3-24, VDE 0482-332-3-24, EN 60332-2-24
Flame retardancy test
IEC 60332-1-2, VDE 0482-332-1-2, BS EN 60332-1-2
Fire resistance test (FE180)
IEC 60331-21
From the Camcom datasheet. The datasheet for the chosen part number is the reference.